Quiz · Hard
Numerical problems on per-unit conversion, power flow, fault current, economic dispatch, inertia and loading.
A balanced three-phase 400 V (line-to-line) load draws 10 A at 0.8 pf lagging. The real power is
3.2 kW
9.6 kW
5.54 kW
6.93 kW
P = sqrt(3) x 400 x 10 x 0.8 = 5.54 kW. 6.93 kW is the apparent power (kVA).
A 1 kW load has pf 0.8 lagging. To correct the pf to unity, how much capacitive reactive power is needed?
600 var
1250 var
480 var
750 var
Q = P tan(theta) = 1000 x 0.75 = 750 var. 1250 is the apparent power in VA, not a reactive power.
S_base = 100 MVA, V_base = 138 kV. A line has X = 38 ohm. Its per-unit reactance is
0.2 pu
0.38 pu
2 pu
5 pu
Z_base = 138^2 / 100 = 190.4 ohm; 38 / 190.4 = 0.2 pu.
A generator rated 50 MVA with X = 0.2 pu on its own base is converted to a 100 MVA base (same voltage base). Its new reactance is
0.1 pu
0.4 pu
0.2 pu
0.04 pu
New = old x S_new / S_old = 0.2 x 100/50 = 0.4 pu. Dividing instead of multiplying is the common error.
Two buses at 1.0 pu are joined by X = 0.25 pu with a 30 degree angle difference. The real power transferred is
4.0 pu
1.0 pu
2.0 pu
0.5 pu
P = (1 x 1 / 0.25) sin 30 = 4 x 0.5 = 2.0 pu. 4.0 pu is the 90-degree maximum.
A bus has a Thevenin impedance of j0.1 pu. The three-phase fault current at the bus (prefault voltage 1 pu) is
0.1 pu
1 pu
100 pu
10 pu
I_f = V / Z_th = 1 / 0.1 = 10 pu.
Two generators have incremental costs 20 + 0.1 P1 and 25 + 0.05 P2 ($/MWh, P in MW) and must supply 150 MW in total, with no limits or losses. What is P1?
About 83 MW
50 MW
100 MW
75 MW
Equal incremental cost: 20 + 0.1 P1 = 25 + 0.05(150 - P1) = 32.5 - 0.05 P1, so 0.15 P1 = 12.5 and P1 = 83.3 MW (P2 = 66.7 MW; both marginal costs are $28.33/MWh).
A 100 MVA machine with H = 5 s has stored kinetic energy of
20 MJ
500 MJ
50 MJ
5 MJ
H = KE / S_rating, so KE = 5 x 100 = 500 MJ.
A 100 MW wind farm produces 262 800 MWh in a year (8760 h). Its capacity factor is
3%
60%
30%
262.8%
262800 / (100 x 8760) = 0.30.
A transformer has 200 W core loss and 800 W copper loss at full load. At what fraction of full load is efficiency maximum?
25%
100%
80%
50%
Copper loss scales with load squared: 800 x x^2 = 200 gives x = 0.5.
A line has a surge impedance of 400 ohm. Its surge impedance loading at 345 kV is about
298 MW
860 MW
86 MW
2980 MW
SIL = V^2 / Zc = (345 kV)^2 / 400 = 119 025 / 400 MW = 297.6 MW.
An unbalanced fault involving ground is analyzed. Which networks are connected in series for a single line-to-ground fault?
Only positive
Positive, negative and zero sequence
Positive and negative in parallel
Zero sequence only
For SLG, the three sequence networks are connected in series at the fault point. LL faults connect positive and negative in parallel.
A distance relay Zone 1 is typically set to
120% of the line
50% of the next line
about 80% of the protected line
100% of the line plus the next line
Zone 1 stays under 100% because measurement and line-data errors could otherwise make it trip instantly for faults on the next line.
What does the equal area criterion test?
Steady-state voltage regulation
Power factor
Thermal limits
Transient stability following a fault
It compares the accelerating area during the fault with the decelerating area after clearing; if they can balance before the unstable angle, the machine stays in synchronism.