Numerical problems on step responses, offset, Routh, Ziegler-Nichols tuning, margins, feedforward and RGA.
A first-order system has K = 2, τ = 5 min and receives a step of size 3. The output at t = 10 min is closest to:
5.2
6.0
2.6
3.9
y = KA(1 - e^(-t/τ)) = 6(1 - e^-2) = 6(0.8647) = 5.19.
An underdamped second-order process has ζ = 0.5. The overshoot is closest to:
16%
4.6%
50%
30%
Overshoot = exp(-π(0.5)/√0.75) = exp(-1.814) = 0.163. The decay ratio is the square of that, about 0.027.
The process has K = 2 and uses P-only control with Kc = 4 (first-order process). A unit step in setpoint produces a steady-state offset of:
0.50
0.889
0.111
0
Offset = 1/(1 + KcK) = 1/9 = 0.111. The final output is 8/9 = 0.889; don't confuse the output with the offset.
Three equal first-order lags (τ = 1, K = 1) in a P-only loop. The ultimate gain Ku is:
27
8
6
3
Characteristic equation s³ + 3s² + 3s + 1 + Kc = 0. Routh: 3·3 > 1 + Kc, so Kc < 8. At Kc = 8 the loop is marginally stable.
The ultimate gain is 8 and the ultimate period 10 min. Ziegler-Nichols PID settings are:
Kc = 8, τI = 5 min, τD = 1.25 min
Kc = 3.6, τI = 8.3 min, τD = 0
Kc = 4.8, τI = 10 min, τD = 2.5 min
Kc = 4.8, τI = 5 min, τD = 1.25 min
PID: Kc = 0.6Ku = 4.8, τI = Pu/2 = 5, τD = Pu/8 = 1.25. Option 2 is the PI set.
FOPDT with K = 2, τ = 10 min, θ = 2 min. Ziegler-Nichols open-loop PI gives Kc and τI of:
Kc = 4.5, τI = 3.3 min
Kc = 2.25, τI = 6.7 min
Kc = 1.0, τI = 10 min
Kc = 2.25, τI = 20 min
Kc = 0.9τ/(Kθ) = 0.9(10)/(2 x 2) = 2.25 and τI = 3.33θ = 6.67 min.
A loop has |G(jω)| = 0.25 at the frequency where the phase is -180°. Its gain margin is:
0.75
0.25
4
2
GM = 1/|G(jω180)| = 4, meaning the gain can be raised fourfold before instability.
The final value of Y(s) = 5/[s(2s+1)] is:
2.5
0
5
Infinite
y(∞) = lim s→0 sY(s) = 5/(0 + 1) = 5.
The inverse Laplace transform of F(s) = 1/[s(s+2)] is:
2(1 - e^(-t))
1 - e^(-2t)
(1 - e^(-2t))/2
e^(-2t)/2
Partial fractions: 1/[s(s+2)] = (1/2)[1/s - 1/(s+2)], giving (1 - e^-2t)/2.
G_p = 2/(3s+1) and the disturbance path G_d = 0.5/(3s+1). The ideal feedforward controller is:
-4
-0.25/(3s+1)
-0.25
+0.25
G_ff = -G_d/G_p = -(0.5/(3s+1))/(2/(3s+1)) = -0.25. The lags cancel.
A 2x2 system has steady-state gains K11 = 2, K12 = 1, K21 = 1, K22 = 2. The RGA element λ11 is:
1.33
0.5
2.0
0.75
λ11 = K11K22/(K11K22 - K12K21) = 4/3 = 1.33, so pairing 1-1 is acceptable though interaction exists.
A cascade inner loop disturbance reaches the outer variable with a time constant of 20 min. The inner loop should have a time constant of about:
4 to 7 min or less
20 min
It does not matter
60 min
The secondary loop should be several times faster (3 to 5 or more), so about 4 to 7 min or less.
A control valve with Cv = 50 (gpm/psi^0.5) passes water (SG = 1) at ΔP = 16 psi. The flow is:
200 gpm
800 gpm
50 gpm
12.5 gpm
Q = Cv sqrt(ΔP/SG) = 50 x 4 = 200 gpm.
A signal contains frequencies up to 10 Hz. The minimum sample rate to avoid aliasing is:
10 Hz
100 Hz
5 Hz
Just over 20 Hz
Sampling must exceed twice the highest frequency: f_s > 20 Hz. At exactly 10 Hz there is aliasing.